A-12 DeviceNet Information
Publication 198-UM002A-EN-P December 2001
Instance 111
Assembly instance 111 is for use with DeviceLogix, and contains 32 consumed network bits.
It is provided for gland plate systems that want to use a standard fixed size assembly, and need
to take advantage of all of the consumed network bits in their DeviceLogix program.
Assembly instance 111 has the following format:
Table A.18 Instance 111 — Byte-wise Fragmented DeviceLogix Output Assembly
for Cat. No. 198-DNG
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Module 1 data
1 Module 2 data
2 Module 3 data
3 Module 4 data
4 Module 5 data
5 Module 6 data
6 Consumed Network Bits 18
7 Consumed Network Bits 916
8 Consumed Network Bits 1724
9 Consumed Network Bits 2532