5-9 Specifications
Publication 198-UM002A-EN-P December 2001
Assembly Instances 104 and 105 are default for 198-DNG. Assembly Instances 106 and 107
are default for 198-DN.
Figure 5.5 198-IB2S Electrical and Application Schematic
Table 5.6 198-IB2S I/O Produced/Consumed Data
Input Data — Assembly Instance 103, 105, or 107
Bit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
————OpenShortInput2Input1
Input Data — Assembly Instance 101
Bit 3 or 7 Bit 2 or 6 Bit 1 or 5 Bit 0 or 4
Open Short Input 2 Input 1
Output Data — Assembly Instance 102, 104, or 106
Bit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
————————
Output Data — Assembly Instance 100
Bit 3 or 7 Bit 2 or 6 Bit 1 or 5 Bit 0 or 4
Compressed format, no data sent
Table 5.7 198-IB2S Specifications
Connector (M12 Female 5-Pin)
M12 Mounting Hole 16 mm (5/ 8 in.) M12
M12 Thread M12x 1mm
M12 Connector Torque 1.4 Nm (12 lb-in.)
Electrical
1
2
3
4
2
1
4
3
Female
Male
2
1
4
3
Male
LOAD
-
-
Op en/Short
Lo gi
c
Input 1
Input2
198-IB2S
+V DC OUT
1
2
3
4
Female
Typical 3-wire sourcing proximity sensor connected to 198-IB2S module
Typical Wiring