3-11 Operation
Publication 198-UM002A-EN-P December 2001
2. You will see a list that contains all of the available devices in the scanlist screen.
Highlight the device you wish to map (in this example, the MDSA is selected from the
Available Devices box), and press the “>” button. This will cause the device (in this
case, the MDSA) to appear in the Scanlist box as shown below:
3. Highlight the MDSA in the Scanlist box, and select the (GLW,23DUDPHWHUV button.
The following screen will appear:
4. Enter the value of the Consumed IO Size parameter in the “Tx Size” box. Enter the
value of the Produced IO Size parameter in the “Rx Size” box. Click 2..
5. Select the 'RZQORDGWR6FDQQHU button in the Scanlist screen. The following screen
appears: