3-3 Operation
Publication 198-UM002A-EN-P December 2001
The user is now able to configure the MDSA. The following steps outline how to accept the
configuration of the I/O modules. This will result in the I/O Status LED changing from
solid red to off.
1. Double click on the MDSA icon. RSNetWorx will verify the identity of the device,
and then display the following screen:
2. Select the “Parameter” tab. RSNetWorx will prompt the user to upload the
parameters from the device. Select the 8SORDG button. The following screen appears:
3. From the screen shown, verify that the number of I/O modules and the names of the
modules recognized are correct. Select the Accept Config parameter (parameter 48 or
58). Double click the value of that parameter. A drop-down list of options will appear.
Select the Accept Config option.
4. Select the $SSO\ button. RSNetWorx will ask you whether it should download the
changes to the device. Select <HV. The device will reset, and the I/O Status LED will
turn off. The MOD/NET status LED will be flashing green, waiting to establish
connections to other nodes.