3-9 Operation
Publication 198-UM002A-EN-P December 2001
screen below shows the Produced IO Assy parameter in the parameter list of a Cat. No.
198-DNG module.
After the Produced IO Assembly has been chosen and downloaded to the MDSA, select $OO
and 8SORDGIURP'HYLFH. This will update the I/O Produced Size parameter value
(parameter 49 or 39). Record this value to be used later in the Scanner I/O mapping.
IMPORTANT
The Produced IO Assy parameter value can not be changed while the
MDSA is online with a scanner. Any attempts to change the value of this
parameter while online with a scanner will result in the error message
“Object State Conflict”.