Publication 2098-RM003A-EN-P October 2001
2-106 Command Reference
Analog Output Override Enable/Disable
Analog Output Override Value
Format: :aa04Efddmmcc<cr>
Parameter
Code:
0x04E
Valid Function
Codes:
0x0 = Read Working Value
0x1 = Write Working Value
0x8 = Read Minimum Value
0x9 = Read Maximum Value
Valid Exception
Codes:
0x08 = Invalid Function Code
Data Fields: dd Enable/disable for overriding the analog output,
where:
0x00: Normal operation
0x01: Override the analog output.
Minimum
Value:
0x00
Maximum
Value:
0x01
Default: 0x00
Format: :aa04Ffddddcc<cr>
Parameter
Code:
0x04F
Valid Function
Codes:
0x0 = Read Working Value
0x1 = Write Working Value
0x8 = Read Minimum Value
0x9 = Read Maximum Value
Valid Exception
Codes:
0x04 = Data Below Minimum
0x05 = Data Above Maximum
0x08 = Invalid Function Code
Data Fields: dddd Analog output override value, in mV.
Minimum
Value:
-10000
Maximum
Value:
10000
Default: 0