Rockwell-automation 2098-DSD-xxx Ultra3000 Host Commands for Serial In Manual de usuario Pagina 79

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 176
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 78
Publication 2098-RM003A-EN-P October 2001
Command Reference 2-63
Motor Intermittent Current
Motor Continuous Current
Format: :aa039fddddcc<cr>
Parameter
Code:
0x039
Valid Function
Codes:
0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value
Valid Exception
Codes:
0x04 = Data Below Minimum
0x05 = Data Above Maximum
0x08 = Invalid Function Code
Data Fields: dddd Motor intermittent current rating, in units of
Amps*128.
Minimum
Value:
0x0001
Maximum
Value:
0x7FFF
Default: 2560
Format: :aa03Afddddcc<cr>
Parameter
Code:
0x03A
Valid Function
Codes:
0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value
Valid Exception
Codes:
0x04 = Data Below Minimum
0x05 = Data Above Maximum
0x08 = Invalid Function Code
Data Fields: dddd Motor continuous current rating, in units of
Amps*128.
Minimum
Value:
0x0001
Maximum
Value:
0x7FFF
Default: 640
Vista de pagina 78
1 2 ... 74 75 76 77 78 79 80 81 82 83 84 ... 175 176

Comentarios a estos manuales

Sin comentarios