Publication 2098-RM003A-EN-P October 2001
Command Reference 2-27
Preset Current
Format: :aa05Cfnnddddcc<cr>
Parameter
Code:
0x05C
Valid Function
Codes:
0x0 = Read Working Value
0x1 = Write Working Value
0x2 = Read Non-Volatile Value
0x3 = Write Non-Volatile and Working Values
0x4 = Copy Non-Volatile Value to Working Value
0x5 = Copy Working Value to Non-Volatile Value
0x6 = Read Default Value
0x7 = Copy Default Value to Non-Volatile and Working Values
0x8 = Read Minimum Value
0x9 = Read Maximum Value
0xA = Read Minimum Array Index Value
0xB = Read Maximum Array Index Value
Valid Exception
Codes:
0x03 = EEPROM Write Error
0x04 = Data Below Minimum
0x07 = Invalid Array Index
0x08 = Invalid Function Code
Data Fields: nn Array index
dddd Preset current, in units of Amps*128.
Minimum
Value:
0x8001
Maximum
Value:
0x7FFF
Minimum Array
Index Value:
0x00
Maximum Array
Index Value:
0x07
Default: 0x0000