146 Rockwell Automation Publication PFLEX-RM002D-EN-E - August 2013
Chapter 1 Detail Drive Configuration and Operation
Table 12 - Resolver Sample Interval
Parameter 270 [Reslvr0 SpdRatio] specifies the speed ratio for the resolver
option card at port 0. The speed ratio comes from the following formula.
Speed ratio = electrical revolutions / mechanical revolutions = pole count / 2.
Parameter 271 [Reslvr0 Carrier] specifies the resolver carrier frequency for the
resolver option card at port 0.
Parameter 272 [Reslvr0 In Volts] specifies the resolver input voltage for the
resolver option card at port 0.
Parameter 273 [Rslvr0 XfrmRatio] specifies the resolver transform ratio for the
resolver option card at port 0.
Parameter 274 [Reslvr0 CableBal] specifies the resolver cable balance for the
resolver option card at port 0.
Bit 15 14 13 12 Resolver Sample Interval Settings
00000.5 ms
00010.5 ms (min. setting)
00101.0 ms
00111.5 ms
01002.0 ms (default setting)
01012.5 ms
01103.0 ms
01113.5 ms
10004.0 ms
10014.5 ms
10105.0 ms
10115.5 ms
11006.0 ms (max. setting)
11016.0 ms
11106.0 ms
11116.0 ms