Rockwell-automation 20D PowerFlex 700S with Phase I Control Reference Manual de usuario Pagina 42

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 190
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 41
42 Rockwell Automation Publication PFLEX-RM002D-EN-E - August 2013
Chapter 1 Detail Drive Configuration and Operation
Figure 8 - Reading Floating-Point Explicit Message Data in an SLC/PLC-5
Figure 9 - Writing Floating-Point Explicit Message Data in an SLC/PLC-5
Digital Inputs
Technical Information
There are four digital inputs on the I/O board. One of the inputs is dedicated for
the Enable and cannot be configured. The other three inputs can be configured.
Digital Input 1 is 24VDC and Digital Inputs 2 and 3 can accept a 12…24VDC
signal. There is a 24VDC power supply on the I/O board to supply power for
those inputs.
Digital Inputs 2 and 3 are high speed digital inputs with a maximum input
frequency of 350 kHz.