134 Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013
Appendix B Adapter Parameters
78 [Logic Src Cfg]
Controls which of the peer-to-drive Datalinks contain the Logic
Command for the drive. The value zero specifies that none of the
Datalinks contain the drive’s Logic Command. Non-zero values
specify the ‘index’ for the Datalink containing the drive’s Logic
Command. For example, if Parameter 76 - [DLs Fr Peer Cfg]
has the value 3 specifying that Datalinks 14…16 are allocated
for peer I/O and Parameter 78 - [Logic Src Cfg] has the value 1
specifying that the first peer I/O Datalink contains the drives
Logic Command, then Datalink 14 contains the drive’s Logic
Command.
NOTE: The adapter allows the peer input configuration
parameters to be written while peer inputs are running.
However, the changes will not take effect until peer inputs are
disabled and then re-enabled, or until the adapter is power
cycled or reset.
Default: 0
Minimum: 0
Maximum: 16
Type: Read/Write
Reset Required: No
79 [Ref Src Cfg]
Controls which of the peer-to-drive Datalinks contain the
Reference for the drive. The value zero specifies that none of the
Datalinks contain the drives Reference. Non-zero values specify
the ‘index’ for the Datalink containing the drive’s Reference. For
example, if Parameter 76 - [DLs Fr Peer Cfg] has the value 3
specifying that Datalinks 14…16 are allocated for peer I/O and
Parameter 79 - [Ref Src Cfg] has the value 1 specifying that
the first peer I/O Datalink contains the drives Reference, then
Datalink 14 contains the drive’s Reference.
NOTE: The adapter allows the peer input configuration
parameters to be written while peer inputs are running.
However, the changes will not take effect until peer inputs are
disabled and then re-enabled, or until the adapter is power
cycled or reset.
Default: 0
Minimum: 0
Maximum: 16
Type: Read/Write
Reset Required: No
80 [Fr Peer Timeout]
Sets the timeout for a peer I/O connection. If the time is reached
without the adapter receiving (consuming) a message, the
adapter will respond with the action specified in Parameter 56
- [Peer Flt Action].
In an adapter receiving (consuming) peer I/O, the value of this
parameter must be greater than the product of the value of
Parameter 89 - [To Peer Period] in the adapter transmitting
(producing) peer I/O multiplied by the value of Parameter 90 -
[To Peer Skip] in the adapter transmitting (producing) peer I/O.
NOTE: The adapter allows the peer input configuration
parameters to be written while peer inputs are running.
However, the changes will not take effect until peer inputs are
disabled and then re-enabled, or until the adapter is power
cycled or reset.
Default: 10.00 Seconds
Minimum: 0.01 Seconds
Maximum: 10.00 Seconds
Type: Read/Write
Reset Required: No