Rockwell-automation 20G PowerFlex 755 Drive Embedded EtherNet/IP Adapt Manual de usuario Pagina 168

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 190
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 167
168 Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013
Appendix C EtherNet/IP Objects
TCP/IP Interface Object
Class Code
Services
Instances
The adapter supports one instance of the TCP/IP Interface object.
Class Attributes
Instance Attributes
Hexadecimal Decimal
0xF5 245
Service Code Implemented for: Service Name
Class Instance
0x0E Yes Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
Number Description
0 Class Attributes
1 Object Attributes
Attribute ID Access Rule Name Data Type Description
1 Get Revision UINT The revision of this object
Attribute ID Access Rule Name Data Type Description
1 Get Status of TCP/IP Network
Interface
UDINT 0 = Not configured
1 = Valid configuration
2…15 = Reserved
2 Get Configuration Capability UDINT Bit | Value (0 = False, 1 = True)
0 = Supports BOOTP
1 = DNS Client (able to resolve host names by query
to DNS server)
2 = DHCP Client (able to obtain network configuration
through DHCP)
3 = DHCP-DNS Update (able to send its host name in
the DHCP request)
4 = Configuration Settable (able to set the network
configuration via TCP/IP object)
5…31 = Reserved
3 Set Configuration Control UDINT Bit | Value
0…3 = Startup configuration
0 = Use configuration saved in NVS
1 = Obtain configuration via BOOTP
2 = Obtain configuration via DHCP
3…15 = Reserved
4 = DNS Enabled (resolves host names by query to
DNS server)
5…31 = Reserved
Vista de pagina 167
1 2 ... 163 164 165 166 167 168 169 170 171 172 173 ... 189 190

Comentarios a estos manuales