Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013 77
Configuring the I/O Chapter 4
Figure 9 - Input Image Controller Tags
Figure 10 - Output Image Controller Tags
Save the I/O Configuration to the Controller
After adding the bridge and drive/adapter to the I/O configuration, you must
download the configuration to the controller. You should also save the
configuration to a file on your computer.
TIP
When using RSLogix 5000 software, version 16.00 or later, you can add the I/O
configuration of a Generic Profile while the controller is online and in the Run
mode.