Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013 23
Installing the Adapter Chapter 2
2. Use drive Parameter 545 - [Speed Ref A Sel] to set the drive speed
Reference.
a. Set the Port field to ‘0 - PowerFlex 755’ as shown below.
b. Set the Parameter field to point to the port in which the embedded
EtherNet/IP adapter is located (always ‘Port 13 Reference’ – the drive
port dedicated to the embedded EtherNet/IP adapter).
The number ‘877’ in the Parameter field of the example dialog box
above is the parameter in the drive that points to the port.
3. Verify that drive Parameter 930 - [Speed Ref Source] is reporting that the
source of the Reference to the drive (Port 0) is the port in which the
embedded EtherNet/IP adapter resides (always ‘Port 13 Reference’).
This ensures that any Reference commanded from the network can be
monitored by using drive Parameter 002 - [Commanded SpdRef ]. If a
problem occurs, this verification step provides the diagnostic capability to
determine whether the drive/embedded adapter or the network is the
cause.
4. If hard-wired discrete digital inputs are not used to control the drive, verify
that all unused digital input drive parameters are set to ‘0’ (Not Used).