58 Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013
Chapter 4 Configuring the I/O
2. Click the Drive tab.
3. Click Connect to Drive to begin the correlation process.
After the drive configuration data has been verified, a pop-up dialog box
will appear to synchronize ports from the online drive to the project to be
sure that the correct Datalinks are assigned.
4. Click OK.
If the Differences Found dialog box appears—which is typical, click
Download. This will download the project settings from the controller to
the drive and its connected adapter. If Upload is clicked, the drive and
adapter settings are uploaded to the controller.
5. The I/O Configuration Differences dialog box appears.
TIP
On subsequent connections to the drive (after the initial download),
click Upload.