Rockwell-automation 20G PowerFlex 755 Drive Embedded EtherNet/IP Adapt Manual de usuario Pagina 27

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 190
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 26
Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013 27
Configuring the Adapter Chapter 3
1. Verif y that Parameter 36 - [BOOTP] is set to ‘1’ (Enabled).
2. Note the adapter’s hardware Ethernet Address (MAC), which will be used
in step 7.
There are two ways to do this:
Remove the PowerFlex 755 drive cover and locate the adapter’s
hardware Ethernet Address (MAC) label on the drive’s Main Control
Board (Figure 4
).
Figure 4 - Adapter Hardware Address Label Location
Use the HIM to scroll to drive Port 13 and access the embedded
EtherNet/IP adapter DIAGNOSTIC folder screen. Then scroll to
Diagnostic Items 43…48 (HW Addr 1…6) to view the adapter’s
hardware Ethernet Address (MAC). Finally, convert these decimal
values to a hex value.
3. On a computer connected to the EtherNet/IP network, start the
BOOTP/DHCP software.
The BOOTP/DHCP Server dialog box appears.
Value Setting
0Disabled
1Enabled (Default)
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲▼
Edit BOOTP
Enabled 1
0<<1
0
9
8
2
1
Ethernet Address
(MAC) label location
Drive Control Pod
Ethernet
Connector
Vista de pagina 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 ... 189 190

Comentarios a estos manuales

Sin comentarios