Document: 553633
ICSTT-RM405f-EN-P
Issue 07
5-17
3) Click the button adjacent to the Channel Variable fields.
4) Choose a data structure from the three options displayed: Simple, Compact,
Full.
The Select Variables dialog box opens.
5) Select a named structure, click OK.
6) Repeat steps 2 to 5 for each channel you want to wire.
Wire Variables to Analogue Input Channels
To wire variables to analogue input channels do the following:
1) Select an analogue input module on the I/O bus.
The module status variable <tagname> that you assigned will appear in the
Variable field.
2) Select the channel that you want to wire to a variable.
3) Click the button next to the channel variable fields.
4) Choose a data structure from the three options displayed: Simple, Compact,
Full.
The Select Variables dialog box is displayed.
5) Select a named structure, click OK.
6) Repeat steps 2 to 5 for each channel.