4-28
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
Configure the Controller Modbus Slaves
You have to configure the communication parameters for each Modbus slave you
implement within the AADvance controller.
To configure a Modbus Slave do the following:
1) Select the Modbus Slaves tab.
The 9110 Modbus Slaves Editor dialog box opens.
2) In the Name column, locate the processor and slave you wish to configure.
3) Set the Connection field, click Apply.
The Id, Port and Protocol fields are set to their default values.
4) If you set the Connection to a serial port, the Id field represents the Slave ID; set
the Id field or accept the default value.