Rockwell-automation AADvance Controller Configuration Guide Manual de usuario Pagina 117

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 286
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 116
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
5-19
Wire Variables to Analogue Output Channels
To wire variables to analogue output channels do the following:
1) Select a analogue output module on the I/O bus.
The module status variable <tagname> appears in the Variable field.
2) Select the channel that you want to wire to a variable.
3) Click the button next to the Channel Variable fields.
4) Choose a data structure from the three options displayed: Simple, Compact,
Full.
The Select Variables dialog box is displayed.
5) Select a named structure, click OK.
6) Repeat steps 2 to 5 for each channel.
Configuring Digital Inputs
You can wire digital input channels to the following variable type and data structures:
BOOL (the <variable_name> gives the input state)
T9K_DI_Compact (provides three elements)
T9K_DI_Full (six elements)
The structures provide additional information about the input, such as line fault status
and discrepancy status. You can also define custom thresholds for digital inputs.
Vista de pagina 116
1 2 ... 112 113 114 115 116 117 118 119 120 121 122 ... 285 286

Comentarios a estos manuales

Sin comentarios