4-26
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
If you select Unicast mode for a processor the controller will wait to be
polled by a client and then respond with a time signal; it will not broadcast any
time signals.
If you select Broadcast mode for a processor the controller will regularly
braodcast: it will also respond to unicast polling requests on that interface.
Note: If you set a processor Broadcast IP Address to zero (0.0.0.0) it will disable
the server on that interface.
3) Set the Broadcast IP Address for the network.
4) Repeat steps 2 and 3 for each additional processor module.
5) Click Apply.