8-14
Document: 553633
ICSTT-RM405f-EN-P
Issue 07
Configuration Guide (AADvance Controller)
Set the RSLogix UNICAST Configuration
The AADvance controller uses the Unicast mode for CIP You will need to configure
the Unicast option in the RSLogix CLX configuration.
Produced Variable
Select a CLX configuration Produced CIP variable.
Check the Allow Unicast Consumer Connections.
Consumed variable
For a Consumed Variable select a Consumed CIP variable.
1) Set the RPI value to 500.0 ms. (the default value is 20.0 ms).
2) Check the Use Unicast Connection over Ethernet IP.