Document: 553633
ICSTT-RM405f-EN-P
Issue 07
4-49
RTC Status: Day of Month
Direction: input to application from controller
Type: word
Values:
1 to 31, or 0 (see description)
Description:
Reports the oldest value of real-time clock (RTC) day of the month as voted by every
9110 processor module which is present and synchronized. Only updated if the real-
time clock control Boolean RTC Read is set to TRUE. If RTC Read is FALSE, the value
will be 0 (zero).
RTC Status: Hours
Direction: input to application from controller
Type: word
Values:
0 to 23
Description:
Reports the oldest value of real-time clock (RTC) hours as voted by every 9110
processor module which is present and synchronized. Only updated if the real-time
clock control Boolean RTC Read is set to TRUE. If RTC Read is FALSE, the value will
be 0 (zero).
RTC Status: Minutes
Direction: input to application from controller
Type: word
Values:
0 to 59
Description:
Reports the oldest value of real-time clock (RTC) minutes as voted by every 9110
processor module which is present and synchronized. Only updated if the real-time
clock control Boolean RTC Read is set to TRUE. If RTC Read is FALSE, the value will
be 0 (zero).