6) Select the Control Booleans rack and ensure that the Channel 3 is wired to
the HART_CONTROL Boolean variable.
7) Select the Analogue Input module you want to use for the HART messages and
select a channel.
8) Select the HART tab.
9) Click on the Enable HART on this channel to put a tick in the box.
10) Wire the Channel to the AIM_HART_FULL variables that you set up in the
dictionary.