146 Publication ICM-UM002F-EN-E - March 2013
Appendix B CIP Objects
Services
(1)
Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.
7 Get/Set Trigger
Hysteresis
REAL The amount of hysteresis
around the trigger level.
In Auto Trigger mode, this
value is a percentage of the
peak-to-peak input signal and
can range from 0 to 50%. In
Manual Trigger mode, this
value is a voltage level (the
hysteresis voltage is added or
subtracted to the threshold
voltage to determine the
hysteresis range).
8 Get/Set Name STRING2 A name to help identify
this channel.
18 characters maximum
10 Get/Set Fault Time-out USINT Number of seconds with
no pulses before a Tach
Fault is indicated unless
Zero Pulse Fault Inhibit
is set to 1.
1 to 64 seconds
11 Get/Set Zero Pulse Fault
Inhibit
BOOL Lack of Tach Pulses does
not cause a Tach Fault.
0 = A lack of tach pulses
constitutes a Tach Fault
1 = A lack of tach pulses does
not constitute a Tach Fault
Table B.46 Tachometer Channel Object Instance Attributes
Attr ID
Access
Rule Name Data Type Description Semantics
Table B.47 Tachometer Channel Object Services
Service
Code Class/Instance Usage Name Description
0E
h
Instance Get_Attribute_Single Returns a single attribute.
10
h
Instance Set_Attribute_Single
Sets a single attribute.
(1)