Publication ICM-UM002F-EN-E - March 2013 29
Installing the XM Dynamic Measurement Module Chapter 2
8 Not Connected
9 Functional Earth Connection to DIN rail ground spring or panel mounting hole
10 Not Connected
11 Not Connected
12 Functional Earth Connection to DIN rail ground spring or panel mounting hole
13 Not Connected
14 Not Connected
15 Functional Earth Connection to DIN rail ground spring or panel mounting hole
Channel 1
16 Xducer 1 (+) Vibration transducer 1 connection
17 Xducer 1 (-) Vibration transducer 1 connection
18 Functional Earth Connection to DIN rail ground spring or panel mounting hole
19 Xducer 1 Pwr 24V (-) Transducer power supply output, negative side; used to power external
sensor; 20 mA maximum load
-24V relative to Signal Common (terminal 41)
20 Xducer 1 Pwr 24V (+) Transducer power supply output, positive side; used to power external
sensor; 20 mA maximum load
21 Buffer 1 (+) Vibration signal 1 buffered output
22 Buffer Output RTN Vibration buffered output return
23 Not Connected
24 Not Connected
25 Functional Earth Connection to DIN rail ground spring or panel mounting hole
26 Not Connected
XM Bus
(see
page 47 for
wiring)
27 CAN_High XM Bus connection, high differential (white wire)
28 Shield bare wire
29 CAN_Low XM Bus connection, low differential (blue wire)
30 XM Bus Common XM Bus bus power input, negative side (black wire)
31 Not Connected
32 Not Connected
33 Not Connected
Terminal Block Assignments
No. Name Description