Rockwell-automation 1440-DYN02-01RJ XM Dynamic Measurement Module Manual de usuario Pagina 42

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 160
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 41
42 Publication ICM-UM002F-EN-E - March 2013
Chapter 2 Installing the XM Dynamic Measurement Module
Connecting an IEPE Accelerometer and Non-Contact Sensor
The following figure shows the wiring of an IEPE accelerometer to channel 0
and the wiring of a non-contact sensor to channel 1.
Figure 2.22 IEPE Accelerometer and Non-Contact Sensor Wiring
ATTENTION
You may ground the cable shield at either end of the cable. Do
not ground the shield at both ends. Recommended practice is to
ground the cable shield at the terminal base and not at the
transducer. Any convenient Functional Earth terminal may be
used. See Terminal Block Assignments on page 28
.
IMPORTANT
Make certain the Power parameter for each channel is set
correctly. Set channel 0 Power to IEPE and set channel 1
Power to -24V. See
Configure the Channel Properties on
page 64 for details.
TYPICAL WIRING FOR IEPE ACCELEROMETER AND NON-CONTACT
SENSOR TO XM DYNAMIC MEASUREMENT MODULE
Channel 0 Input Signal
Channel 1 Input Signal
Vista de pagina 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 159 160

Comentarios a estos manuales

Sin comentarios