
34 Publication ICM-UM002F-EN-E - March 2013
Chapter 2 Installing the XM Dynamic Measurement Module
Connecting the Buffered Outputs
The Dynamic Measurement module provides buffered outputs of all
transducer input signals. The buffered output connections may be used to
connect the module to portable data collectors or other online systems.
Figure 2.11
shows the buffered output connections for the module.
Figure 2.11 Buffered Output Connections
Connecting the Transducer
The module can accept input from any Allen-Bradley non-contact eddy
current probe, a standard IEPE accelerometer, a velocity transducer, AC
voltage output, or a DC voltage output measurement device.
Connecting an IEPE Accelerometer
The following figures show the wiring of an IEPE accelerometer to the
terminal base unit.
You may ground the cable shield at either end of the cable. Do
not ground the shield at both ends. Recommended practice is to
ground the cable shield at the terminal base and not at the
transducer. Any convenient Functional Earth terminal may be
used. See Terminal Block Assignments on page 28
.
Make certain the Power parameter is set to IEPE so power is
provided to the transducer. See
Configure the Channel
Properties on page 64 for details.
Comentarios a estos manuales