Publication ICM-UM002F-EN-E - March 2013 43
Installing the XM Dynamic Measurement Module Chapter 2
Connecting Two Accelerometers and a Non-Contact Sensor
The following figure shows the wiring of two IEPE accelerometers and a
non-contact sensor to the terminal base. The IEPE accelerometers are wired
to channel 0 and channel 1. The non-contact sensor is wired to the tachometer
input signal.
ATTENTION
You may ground the cable shield at either end of the cable. Do
not ground the shield at both ends. Recommended practice is to
ground the cable shield at the terminal base and not at the
transducer. Any convenient Functional Earth terminal may be
used. See Terminal Block Assignments on page 28
.
IMPORTANT
Make certain the Power parameter is set to IEPE for both
channel 0 and channel 1 so power is provided to the
accelerometers. See
Configure the Channel Properties on
page 64 for details.
IMPORTANT
Transducer DC bias is monitored on all signals.