Installing the XM Dynamic Measurement Module Chapter 2
Figure 2.15 Non-contact Sensor to Channel 1 Wiring
Connecting a Passive Transducer
The following figures show the wiring of a passive transducer, such as a
velocity sensor, to the terminal base unit.
TYPICAL WIRING FOR NON-CONTACT SENSOR
TO XM DYNAMIC MEASUREMENT MODULE CHANNEL 1
Channel 1 Input Signal
Signal Common
Shield
-24V DC
You may ground the cable shield at either end of the cable. Do
not ground the shield at both ends. Recommended practice is to
ground the cable shield at the terminal base and not at the
transducer. Any convenient Functional Earth terminal may be
used. See Terminal Block Assignments on page 28
.
The module does not power the sensor. It measures only the
input voltage.
Make certain the Power parameter is set to Bias Current.
See
Configure the Channel Properties on page 64 for details.