Publication 1753-PM001A-EN-P - November 2005
B-4 Configure the GuardPLC OPC Server
7. Drag G16OPC01 onto the OPC-Server Resources Editor.
The Specify HH-Network Configuration for OPC dialog opens.
8. Click OK.
Connect Signals
1. Choose the Signals pulldown menu from the menu bar and
choose Editor.
2. Add two new signals:
DI1 - input sent to the OPC Server
DO1 - output sent from the OPC Server
3. Left-click 1 in the OPC-Server Resources Editor. Choose Connect
OPC-Signals.
4. Drag DO1 from the Signal Editor to the Inputs section of the
OPC Signal Connections window.