Publication 1753-PM001A-EN-P - November 2005
2-4 Connect to GuardPLC Distributed I/O Modules
Set I/O Properties
1. In the RSLogix Guard PLUS! Hardware Management window,
right-click the module in the project tree and select Properties.
2. You must change the Rack ID [SRS] to configure the second
portion of the SRS. Change the Rack ID [SRS] value to 1.
3. Click OK.
The offline SRS is now 60000.1. The 60000 comes from the
parent controller, as shown by the arrow in the illustration
above.
Configure the Offline IP Address
1. Expand the module in the project tree.
2. Right-click COM and choose Properties.
3. Change the IP address to match the module.
4. Click OK.