Publication 1753-PM001A-EN-P - November 2005
3-10 Create a GuardPLC Project
Connect Distributed I/O Signals
For distributed I/O modules, you connect signals to the distributed
I/O module’s inputs and outputs just as if they were I/O points on a
controller.
1. Expand the distributed I/O module in the Hardware
Management project tree and right-click on DI for inputs or DO
for outputs.
2. Choose the proper tab, Inputs or Outputs, on the Signal
Connections dialog.
3. Drag and drop signals from the Signal Editor onto the Input or
Output tabs to map the signals to the appropriate terminals on
the distributed I/O module.
Connect Analog Input Signals (GuardPLC 1800 Controllers)
1. Right-click the GuardPLC 1800 controller’s inputs (MI 24/8
FS1000) and choose Connect Signals.
2. In the Signal Editor, create signals for the analog values.