Publication 1753-PM001A-EN-P - November 2005
Configure the GuardPLC OPC Server B-7
6. Set the System ID (SRS) to 1 and click OK.
7. Expand the OPC-Server and double-click IP Address.
8. Set the IP Address to 192.168.0.216 and click OK.
Token Group
1. Right-click Token Group and choose Properties.
2. Change the profile to Medium.
3. Verify that the Token Group ID is 4.
4. Click Apply and then OK.