Publication 1753-PM001A-EN-P - November 2005
Connect to the GuardPLC Controller 1-17
3. Edit the IP address to match the GuardPLC controller and click
OK.
Step 12: Recover from a Controller Fault After Using the Reset
Button
After using the Reset button, the Control Panel appears as follows if
the SRS was not originally 60000 prior to the Reset. The Fault LED on
the front of the GuardPLC controller is illuminated, and the CPU State
of the Resource is STOP/INVALID CONFIGURATION.