Rockwell-automation 1770-KF2 Data Highway or Highway Plus Interface Mo Manual de usuario Pagina 100

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 235
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 99
Message Packet Formats
Chapter 5
5-21
Note that the interface module at the receiving PC station executes this
command by first making a copy of the addressed PC byte. It then sets or
resets the appropriate bits and writes the byte back into PC memory. At
the same time, the PC processor can be changing the states of the original
bits in memory. Because of this, some data bits may unintentionally be
overwritten.
Command
Format:
Reply Format:
TNSSTSCMD
05
SRCDST
TNSSTSCMD
45
SRCDST
ADDR
Up to 60 Masks of
This Form
SET RESET
Unprotected Read
This command reads words of data from any area of PC data table
memory. Use the SIZE field to specify the number of bytes to be read.
To specify a number of PC words, SIZE should be an even value because
PC words are two bytes long.
Command
Format:
Reply Format:
TNSSTSCMD
01
SRCDST
TNSSTSCMD
41
SRCDST
ADDR
DATA
— Max. of 244 Bytes
SIZE
Vista de pagina 99