Installation
Chapter 3
3-5
Figure 3.3
Switch
Settings for Network Link
O
O
12
N
F
F
Both switches ON for
57,600 bits per second
SW–5
13514
Asynchronous Communication Rate and Diagnostic Commands
Switch Assembly SW-6 lets you select the communication rate and
diagnostic commands for the KF2 module’s asynchronous port.
Communication Rate
Set the communication rate switches as shown:
Bits
per
Set Switch:
Second as:
1 2 3
110 OFF OFF OFF
300 ON OFF OFF
600 OFF ON OFF
1,200 ON ON OFF
2,400 OFF OFF ON
4,800 ON OFF ON
9,600 OFF ON ON
Diagnostic Commands
Switch 4 determines how the KF2 module treats diagnostic commands
sent to it by a remote Data Highway station. You can connect the
asynchronous port of the KF2 module directly to a 1771-KG, 1773-KA,
or 1775-KA communication interface module (Figure 1.2). In such
applications, you can set Switch 4 so that the KF2 module either executes
any received diagnostic commands itself or passes those commands to the
other attached communication module.
If
Y
ou W
ant Y
our Module to:
Set Switch 4:
Execute Received Diagnostic Commands
ON
Pass Any Received Diagnostic Commands to the
Attached Asynchronous Device
OFF