Error Reporting
Chapter 7
716
Code (If Applies)
EXT STS
STS
Meaning
Error
Code
PLC3 WRITE COMMANDS
10 81 1.
There are not at least 2 bytes of data after the end of the
block address.
2.
There is an odd number of data bytes after the end of the
block address.
3.
Sum of packet of
fset and size values specifies more than
65,535 words.
4.
Sum of packet of
fset and size is greater than total
transaction size.
30 83
The local 1775KA module has executed a shutdown request.
40 84
Backplane error (either memory parity or timeout/disconnect).
60 86
Keyswitch setting disallows access.
70 87
Local PLC3 is in Program mode.
1 F0 231
There is an error in converting the block address
(major section > 63, context > 15, or section > 15).
2 F0 232
Three or fewer addressing levels specified in a PLC3 word
address.
3 F0 233
Conversion of a file address to a block address resulted in more
than 9 addressing levels.
4 F0 234
Symbolic address not found.
5 F0 235
Symbolic address is of length zero or is longer than 8 bytes.
6 F0 236 1.
Destination file not found.
2.
Destination address does not point to a word (for
wordrange writes) or a file (for file writes).
3.
Destination address specifies more levels than required.
4.
First word of destination location does not exist.
7 F0 237 1.
Any word in the total transaction does not exist in the
destination file.
2.
For a file write, the source and destination files are not the
same size.
8 F0 238
Destination file size changed between packets of a multipacket
transaction and became too small for the total transaction.
9 F0 239
There are more than 65,535 words in the source file.