Rockwell-automation 1770-KF2 Data Highway or Highway Plus Interface Mo Manual de usuario Pagina 189

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 235
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 188
Error Reporting
Chapter 7
734
41. Number of messages with incorrect network address.
42. 16-bit count of messages sent by command initiator.
43. Not used.
44. 16-bit count of commands received by command executor.
45. Not used.
46. 16-bit count of replies sent by command executor.
47. Not used.
48. 16-bit count of replies received by command initiator.
49. Not used.
50. Number of breaks sent to IT.
51. Number of resynchs sent to PC.
1775KA Diagnostic Counters
DATA HIGHWAY PORT
0. Bad CRC on acknowledgment.
1. No acknowledgment before timeout occurred.
2. Contention (while master, detected message transmission by another
station).
3. Acknowledgment contained an error.
4. Returned message (local errors and lost replies).
5. Waits (no “receive” buffer space at destination station).
6. Poll timeout (master failed).
Vista de pagina 188
1 2 ... 184 185 186 187 188 189 190 191 192 193 194 ... 234 235

Comentarios a estos manuales

Sin comentarios