Error Reporting
Chapter 7
714
Code
(If Applies)
EXT STS
STS
Error
Code
Meaning
DIAGNOSTIC READ COMMAND
10 81 1.
A 2byte ADDR field and a 1byte SIZE field are missing
after the FNC byte in the command message.
2.
The number of bytes of data requested in the SIZE field is
greater than the maximum number allowed per reply packet
(244), or SIZE is 0 (zero).
50 85
The command is an illegal request to read from the 1775KA
module'
s backplane window
.
DIAGNOSTIC ST
A
TUS COMMAND
40 84
A backplane error occurred during determination of the physical
address of the end of the ladder diagram program or of the end of
user memory
.
PLC/PLC2 WORD WRITE COMMANDS
10 81 1.
A 2byte ADDR field is expected after the TNS word, but
only one byte is present.
2.
There is an odd number of data bytes in the command
packet.
3.
The ADDR value is odd (that is, it does not specify a word
address).
30 83
The local 1775KA module has executed a shutdown request to
the local PLC3 processor
.
40 84
Local PLC3 backplane error (either memory parity or
timeout/disconnect).
50 85 1.
The destination file does not exist in PLC3 memory
.
2.
The destination word does not exist in the destination PLC3
file.
3.
The length of the destination file is greater than
65, 535 words.
60 86
Local keyswitch setting prohibits writing into desired destination
file.
70 87
The local PLC3 processor is in Program mode. There may or
may not be a major system fault.