Installation
Chapter 3
3-12
must be connected to the GND of the modem or computer. Note that this
type of connection does not provide electrical isolation between the
module and the connected device.
If a connection is made between the KF2 and an RS-422-A compatible
device, you can mount the device and the module up to 4,000 cable-feet
apart.
Direct Connection to a Computer
To connect the module directly to a computer, you can construct your own
cable according to the wiring diagram in Figure 3.6.A. This cable plugs
into the COMPUTER ASYNCHRONOUS connector on the module and
the RS-232-C or RS-422-A compatible connector on the computer
(Figure 3.6.A). Connect the cable shield at one end only. Be sure that the
cable length does not exceed the RS-232-C limit of 50 feet or the
RS-422-A limit of 4,000 feet.
Figure 3.6
Connection
to a Computer
25-Pin Female Connector 25-Pin Male Connector
Cable
Asynchronous
Port Connector
of 1770-KF2
Module (RS-232-C)
A. Connection Diagram
RS-232-C or
RS-422-A
Compatible
Port Connector
of Computer
RDA
RDB
TDA
TDB
Asynchronous
Port Connector
of 1770-KF2 Module
(RS-422-A)
RS-422-A
25-Pin Female
Connector
1
14
25
16
18
4
5
6
8
20
Cable (Not
C. W
iring Diagram for RS-422-A
Exceeding 4,000 Ft.)
Note:
The connector and the pinouts for
the RS-422-A compatible computer
port will depend on the computer
manufacturer’
s standard assignment.
Other pins may have to be jumpered
on the computer connector to ensure
proper operation.
Compatible Port
Connector of
Computer
1
7
3
4
2
5
20
8
Asynchronous
Port Connector
of 1770-KF2 Module
(RS-232-C)
25-Pin Female
1
7
2
4
3
5
6
8
20 6
Cable (Not
Connector
25-Pin Male
Exceeding 50 Feet)
Signal Ground
RXD
TXD
DTR
DCD
DSR
RTS
CTS
Chassis Ground
B. W
iring Diagram for RS-232-C
11309
RS-232-C
Compatible Port
Connector of
Computer
Connector
Comentarios a estos manuales