Message Packet Formats
Chapter 5
5-23
Disable Outputs
This command turns off all outputs of the PLC controller. Use this
command to disable the PLC’s outputs before doing a physical write
operation.
Command
Format:
Reply Format:
TNSSTSCMD
07
SRCDST
TNSSTSCMD
47
SRCDST
FNC
00
Enable Program
This command returns control of outputs to the PLC ladder diagram
program. Use this command to cancel the effect of the disable outputs
command.
Command
Format:
Reply Format:
TNSSTSCMD
07
SRCDST
TNSSTSCMD
47
SRCDST
FNC
01