Message Packet Formats
Chapter 5
5-41
Physical Write with Mask
This command sets or resets bits in a memory word of the selected
controller. The ADDRESS field contains the physical PLC-4 address of
the memory word to be modified. Refer to Chapter 6 for a description of
physical addresses.
The BIT MASK field specifies which bits in the PLC-4 word are to be
modified, and the DATA field specifies whether those bits are to be set or
reset. For each bit that is 1 in the BIT MASK, the corresponding bit in the
addressed PLC-4 word is set to the same value (1 or 0) as the
corresponding bit in the DATA field. For each bit that is 0 in the BIT
MASK, the corresponding bit of the addressed PLC-4 word is left
unchanged.
Note that you can modify up to 40 PLC-4 words in this way by specifying
a series of ADDRESS, DATA, and BIT MASK fields.
Reply
Format:
(EXT STS Byte Optional)
B.
Format When Reporting an Error
TNSSTSCMD
4E
SRCDST
TNSSTSCMD
4E
SRCDST EXT
STS
A.
Format When Successful Execution
Command Format:
TNSSTSCMD
0E
SRCDST FNC
0F
PLC-4
SEL
ADDRESS
(Repeated up to 40
Times)
DATA BIT
MASK
Vista de pagina 119