General Asynchronous Link Error Codes
(STS, EXT STS)
Appendix C
C3
You will have an EXT STS code if your STS code is F0 (hex). The EXT
STS has different definitions depending on the command code (type of
command). If the command code is:
00 to 08 (hex) then there is not an EXT STS byte
09 to 0D (hex) then these command codes are not defined so the EXT
STS code is not defined
0E or 0F (hex) then the codes are defined in the sections below
The following table contains EXT STS codes (in hex) that you may find if
the command code is 0E (hex).
This
Code
Means
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
10
to 1F
20
21
22
23
24
25
26
27
28
29
2A
2B
2C
2D
2E
2F
30 to 7B
7C
7D
7F
80 to FF
MultiDefined Processors on Ring
Processor Is Already Allocated
Processor Must be Allocated for This Command
Extended Function in Progress
Function Not A
vailable in This Processor Command Set
Function Not A
vailable in This Processor Mode
Processor Number in Program and Hardware Do Not Match
Invalid Address
Memory Protection Access V
iolation
Invalid Parameter
Search Unsuccessful
Program Needs to Be Stored  RAM and PROM Do Not Match
External EEPROM Is Defective, Cannot T
ransfer Contents Correctly
Invalid User Program
Not Used
Device Resource Unavailable
Not Used
Processor Already Allocated by Requesting Station
Processor Already Allocated by Another Remote Station
Processor Not Allocated
Data Length Invalid
Data Size T
oo Large
Data Size T
oo Large
Data Size T
oo Small
At Least One of the Addresses Points to a ReadOnly Area
Address Past End of Memory
Memory Protected, Address to Program Area Illegal
Memory Protected, Address to Processor Status Area Illegal
Memory Protected, Address to Protected T
imer or Counter
Processor Not in Program Mode, Address to Program Area
Address Past End of Used Memory"
Program V
alid" Bit Not Set in PLC4 Program ID Byte
Invalid PLC4 Select V
alue
Not Used
PLC4 Ring Disconnected
No PLC4 Response
Invalid PLC4 Select Byte
Not Used
The EXT STS Byte