Message Packet Formats
Chapter 5
5-37
Word Range Write
This is a write command whose starting address is either a word symbol, a
file symbol plus a word offset, or a logical address. This starting address
must point to a word in a file. The function code is 0. A special case of
this command is the single-word write, where the number of bytes to read
is only one word long.
Command Format:
TNSDST SRC CMD 00 00FNC
0F 00
PACKET
OFFSET
TOTAL
TRANS
ASCII SYMBOL
(8 CHARS. MAX.)
DATA — MAX. OF 228 BYTES OR 114 WORDSW/F
00
TNSDST SRC CMD FNC
0F 00
PACKET
OFFSET
TOTAL
TRANS
PLC-3 LOGICAL
ADDRESS
(2-51 Bytes)
DATA
— Max. length is 239 bytes minus the length of the PLC–3 logical address.
STS
(Must be an even number of bytes.)
TNSSTSCMD
4F
SRCDST
TNSSTSCMD
4F
SRCDST EXT
STS
Reply
Format:
(EXT STS Byte Is Optional)
B.
Format When Reporting an Error
A.
Format When Successful Execution
B.
Logical Address
A. W
ord Symbol Address
STS
PLC-4 Commands
PLC-4 stations can execute all of the commands in the basic command
set. They can also execute the following commands, which apply only to
PLC-4 Microtrols:
Allocate Processor
Deallocate Processor
Initialize Processor
Physical Read
Physical Write
Physical Write with Mask
Set to Program Load Mode
Set to Run Mode
Set to Single-Scan Test Mode
Set to Test Mode