Rockwell-automation 1770-KF2 Data Highway or Highway Plus Interface Mo Manual de usuario Pagina 128

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 235
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 127
Message Packet Formats
Chapter 5
5-49
have the privilege of placing the host in a Download mode. This error
occurs when:
the processor is in Program or Run mode (must be in Remote Program
or Remote Run mode),
the processor is being edited, or
some other station is already downloading to the processor.
The format for this message is as follows:
Command
Format:
Reply Format:
TNSSTSCMD
0F
SRCDST
TNSSTSCMD
4F
SRCDST
FNC
3A
EXT
STS
1
1
Flag Byte (Explained Below)
The STS and EXT STS bytes contain status and error code information.
For more information on these bytes, see the “Error Codes” section in this
document.
You use the bits in the flag byte of the set processor command as follows:
Bits 2 through 7 are unused.
Bits 0 and 1 determine which operating mode is selected.
This table shows the settings of Bits 0 and 1 for each operating mode:
For
This Operating Mode: Bit 1 Bit 0
Program/Load Mode (Processor Idle, I/O Disabled)
00
Remote T
est Mode (Processor Scanning, I/O Disabled)
01
Remote Run Mode (Processor Scanning, I/O Enabled)
10
No Change (Only Remote Bit Af
fected) 1 1
Vista de pagina 127
1 2 ... 123 124 125 126 127 128 129 130 131 132 133 ... 234 235

Comentarios a estos manuales

Sin comentarios