122 Rockwell Automation Publication 193-UM011A-EN-P - September 2010
Appendix A Specifications
Ground Fault (E3 Plus) Yes Yes
Communication Fault Yes Yes
Communication Idle Yes Yes
Remote Trip Yes No
Table 10 - Ground Fault Protection
Type Core Balanced
Intended Use Equipment Protection
Classification (Per UL 1053) Class I
Protection Range 20…100 mA
100…500 mA
200 mA…1.0 A
1.0…5.0 A
Trip & Warning Time Delay 0.1…25.0 s
Protection Inhibit Time 0…250 s
Table 9 - Protection
Trip Warning