Rockwell Automation Publication 193-UM011A-EN-P - September 2010 77
Programmable Parameters Chapter 5
Table 19 - Output State Matrix for Output Setup Parameters
Commanded
Output State
Prior to Trip
Out X
PR FltState
Setting
Out X
PR FltValue
Setting
Output State
with Active Trip
Last Commanded
Output State during Trip
Output State Following Trip
Reset
(before any new command)
Open 0 = Go to FltValue 0 = Open Open Open Open
Close Open
-none - Open
1 = Closed Closed Open Closed
Close Closed
-none - Closed
1 = Ignore Fault As Commanded As Commanded As Commanded
Close 0 = Go to FltValue 0 = Open Open Open Open
Close Open
-none - Open
1 = Closed Closed Open Closed
Close Closed
-none - Closed
1 = Ignore Fault As Commanded As Commanded As Commanded
OUTA PR FLTSTATE
This parameter, in conjunction with
Parameter 66, defines how Output A will
respond when a trip occurs. When set to “1”,
Output A will continue to operate as
commanded via the network. When set to
“0”, Output A will open or close as
determined by the setting of Parameter 66.
Parameter Number 65
Access Rule Get/Set
Data Type BOOL
Object Mapping 0x09-1-113
Group DeviceNet I/O
Units
Minimum Value 0 = Go to FltValue (#66)
Maximum Value 1 = Ignore Fault
Default Value 0
OUTA PR FLTVALUE
This parameter determines the state that
Output A assumes when a trip occurs and
Parameter 65 is set to “0”.
Parameter Number 66
Access Rule Get/Set
Data Type BOOL
Object Mapping 0x09-1-114
Group DeviceNet I/O
Units
Minimum Value 0 = Open
Maximum Value 1 = Closed
Default Value 0