66 Rockwell Automation Publication 193-UM011A-EN-P - September 2010
Chapter 5 Programmable Parameters
PM - # Starts
This parameter allows the installer to set a
number of starts after which preventative
maintenance should be performed.
Parameter Number 101
Access Rule Get/Set
Data Type UINT
Object Mapping 29hex-1-106
Group Advanced Setup
Units —
Minimum Value 0
Maximum Value 65535
Default Value 0
GF Warn Delay
This parameter allows the installer to
program a time duration for which a ground
fault condition must exist at the programmed
level prior to the device providing a warning.
Parameter Number 105
Access Rule Get/Set
Data Type USINT
Object Mapping 2Chex-1-180
Group Advanced Setup
Units Seconds
Minimum Value 0
Maximum Value 250
Default Value 0
PM - Oper. Hours
This parameter allows the installer to set the
hours of operation after which preventative
maintenance should be performed.
Parameter Number 102
Access Rule Get/Set
Data Type UINT
Object Mapping 29hex-1-107
Group Advanced Setup
Units Hours
Minimum Value 0
Maximum Value 65535
Default Value 0
UC Inhibit Time
This parameter sets the time in which the
under current protection is inhibited during a
starting sequence.
Parameter Number 107
Access Rule Get/Set
Data Type USINT
Object Mapping 2C
hex
-1-158
Group Advanced Setup
Units Seconds
Minimum Value 0
Maximum Value 250
Default Value 1