Rockwell Automation Publication 193-UM011A-EN-P - September 2010 141
DeviceNet Information Appendix B
Table 58 - Control Supervisor Object Instance Attributes
Attribute
ID
Access
Rule
Name Data
Typ e
Value
10 Get Tripped BOOL
0 = No Fault present
1 = Fault Latched
11 Get Warning BOOL
0 = No Warning present
1 = Warning present (not latched)
12 Get/Set Fault Reset BOOL
0->1 = Trip Reset
otherwise no action
13 Get Trip Code UINT
ODVA Trip Code – In trip state indicates
cause of trip; If not tripped, indicates cause
of last trip.
14 Get Warning Code UINT
ODVA Warning Code - In warning state
indicates cause of warning; If no warning,
indicates cause of last warning.
17 Get/Set Force Trip BOOL
0->1 = Trip. Test trip generated. This
attribute returns object state conflict when
“Test Enable” bitr is set in Trip Enable.
100 Get Elapsed Time UINT
Logs motor-on (Current Present) hours.
101 Get Starts Counter UINT
Logs the number of motor starts.
106 Get/Set PM – Start Count UINT
The Preventative Maintenance Start Count
flag is set after this number of starts
107 Get/Set PM – Oper Hours UINT
The Preventative Maintenance Operating
Hours flag is set after this number of hours
108 Get/Set Test Enable BOOL
Enables/Disables the Test Button.
109 Get Warning Log 0 WORD
Enumerated same as attribute 115
110 Get Warning Log 1 WORD
Enumerated same as attribute 115
111 Get Warning Log 2 WORD
Enumerated same as attribute 115
112 Get Warning Log 3 WORD
Enumerated same as attribute 115
113 Get Warning Log 4 WORD
Enumerated same as attribute 115
114 Get Trip Status WORD
Bit 0 = Test Trip
Bit 1 = Overload
Bit 2 = Phase Loss
Bit 3 = Ground Fault **
Bit 4 = Stall
Bit 5 = Jam
Bit 6 = Underload
Bit 7 = PTC **
Bit 8 = Current Imbal
Bit 9 = Comm Fault
Bit 10 = Comm Idle
Bit 11 = NonVol Mem
Bit 12 = Hardware Fault
Bit 13 = Reserved
Bit 14 = Remote Trip
Bit 15 = Blocked Start
Vista de pagina 139