70 Rockwell Automation Publication 193-UM011A-EN-P - September 2010
Chapter 5 Programmable Parameters
For Catalog Number 193-EC4ZZ
For Catalog Number 193-EC4ZZ
For Catalog Number 193-EC4ZZ
L1 OC Warn Level
This parameter sets the over current warning
level for line 1.
Parameter Number 120
Access Rule Get/Set
Data Type UINT
Object Mapping 2C
hex
-1-171
2C
hex
-1-121
Group Advanced Setup
Units 0.01 Amps
1 Amps
Minimum Value 0.20
Maximum Value 5000
Default Value
L2 OC Trip Level
This parameter sets the over current trip
level for line 2.
Parameter Number 121
Access Rule Get/Set
Data Type UINT
Object Mapping 2C
hex
-1-172
2C
hex
-1-188
Group Advanced Setup
Units 0.01 Amps
1 Amps
Minimum Value 0.20
Maximum Value 5000
Default Value
L2 OC Trip Delay
This parameter allows the installer to
program a time duration for which an over
current condition must exist at the
programmed level prior to the device
tripping.
Parameter Number 122
Access Rule Get/Set
Data Type USINT
Object Mapping 2C
hex
-1-173
Group Advanced Setup
Units 0.1 Seconds
Minimum Value 0.1
Maximum Value 25.0
Default Value 1.0
L2 OC Warn Level
This parameter sets the over current warning
level for line 2.
Parameter Number 123
Access Rule Get/Set
Data Type UINT
Object Mapping 2C
hex
-1-174
2C
hex
-1-122
Group Advanced Setup
Units 0.01 Amps
1 Amps
Minimum Value 0.20
Maximum Value 5000
Default Value